CellarMate 200
|
Unit Performance and Specs
| | |
| Performance |
|
|
| Nominal Tonnage |
Ton |
2 |
| Nominal Compressor |
HP |
2.5 |
| Net Cooling Capacity* |
|
|
| @ 70 DEG F Ambient |
BTUH |
324/355 |
| @ 80 DEG F Ambient |
BTUH |
304/331 |
| @ 90 DEG F Ambient |
BTUH |
282/307 |
| Controls |
|
|
| Type |
12-volt Thermostat |
|
| Accuracy |
+/-2F |
|
| Evaporator Section |
|
|
| Fan Motor Size |
Watts |
240 |
| Rated Air Flow |
CFM |
740 |
| Air Flow with 25' flex duct |
CFM |
715 |
| Condenser Section |
|
|
| Fan Motor Size |
Watts |
240 |
| Rated Air Flow |
CFM |
750 |
| Air Flow with 25' flex duct |
CFM |
720 |
| Electrical Requirements |
|
|
| Power Requirements |
V/P/H |
230/1/60 |
| Current Draw - Cooling Mode |
Amps |
16 |
| Minimum Circuit Size |
Amps |
20 |
| Typical Testing Data |
|
|
| Head Pressure |
psig |
138 |
| Suction Pressure |
psig |
27 |
| Condenser Inlet Temperature |
Deg F |
78 |
| Condenser Outlet Temperature |
Deg F |
107 |
| Evaporator Inlet Temperature |
Deg F |
55 |
| Evaporator Outlet Temperature |
Deg F |
46 |
| ETL Approved - Patent Pending |
|